24kV Air Insulated Switchgear with Draw-Out Vacuum Circuit Breaker

FEATURES
  • Modular construction
  • Extensible
  • Small installation area
  • Easy to operate
  • Operated exclusively from the front
  • Internal arc resistant
  • Equipped with vacuum circuit breaker with increased mechanical and electrical life
  • Several optional equipment available
  • Reduced maintenance and increased reliability
  • Racking-In and racking-out of MV breaker behind arc-proof doors

Electrical Data

Rated voltage: 24 kV

Insulation level

Lightning impulse (1.2/50 µs) : 125 kV peak
Power frequency (50Hz / 1 min): 50 kVrms
Rated frequency : 50 Hz
Rated current : 630 ~ 1600 A
Breaking current : 25 kArms
Making current : 63 kAp
Rated short-time current : 25 for 3s kArms

Mechanical characteristics

Protection degree : IP4X (others on request)
Standard colour : RAL 7035 (others on request)

Normal service conditions

Ambient temperature : basic:-5..+40  °C , options:-10.. +55  °C

Dimensions (2LBS+1CB)

Height : 2350 mm
Depth : 1700 mm
Width : 800 mm